Specifications

Rated Capacity Range 24 HP
Max. Number of Connectable Indoor Units*1 2 - 40
Connectable Capacity of Indoor Units 34.0 - 88.4 kW
Scroll
Power Source Phase 3 phase
Voltage 380-415(50Hz),400(60Hz) V
Frequency 50/60 Hz
Capacity Cooling 68.0 kW
Heating 76.5 kW
Input Power Cooling 18.24 kW
Heating 18.42 kW
EER Cooling 3.73 W/W
COP Heating 4.15 W/W
Airflow Rate 13000 + 11100 m³/h
Sound Pressure Level*2 Cooling 62 dB(A)
Heating 64 dB(A)
Max. External Static Pressure 82 Pa
Compressor Motor Output 11 x 1 + 7.5 x 1 kW
Heat Exchanger Fin Blue fin
Net Dimensions
Height X Width X Depth
1690 x 1240 x 765 mm
1690 x 930 x 765 mm
Net Weight 279 kg
255 kg
Refrigerant Type R410A
Charge 11.8 kg
11.7 kg
Connection Pipe Diameter Liquid φ15.88 mm
Gas φ34.92 mm
Max. Height Difference
(Outdoor Unit: Upper/Lower)
50 / 40 m
Operation Range Cooling -5 to 52 °CDB
Heating -20 to 21 °CDB
Scroll