VRF Systems V-III TROPICAL Series AJH414LNTCHH

Outdoor unit

Outdoor Unit :
AJH144LNTCH
Outdoor Unit :
AJH144LNTCH
Outdoor Unit :
AJH126LNTCH
Download :
Catalogues

Features

  • High ambient operation design
  • Energy-saving technologies for boosting operational efficiency
  • Elaborate anti-corrosion treatment
  • Outstanding cooling capacity


Specifications

Rated Capacity Range 46 HP
Max. Number of Connectable Indoor Units*1 2 - 55
Connectable Capacity of Indoor Units 65.0 - 169.0 kW
Scroll
Power Source Phase 3 phase
Voltage 380-415(50Hz),400(60Hz) V
Frequency 50/60 Hz
Capacity Cooling 130.0 kW
Heating 145.0 kW
Input Power Cooling 36.98 kW
Heating 38.43 kW
EER Cooling 3.52 W/W
COP Heating 3.77 W/W
Airflow Rate 13700 + 13700 + 13000 m³/h
Sound Pressure Level*2 Cooling 66 dB(A)
Heating 68 dB(A)
Max. External Static Pressure 82 Pa
Compressor Motor Output 11 x 1 + 11 x 1 + 11 x 1 kW
Heat Exchanger Fin Blue fin
Net Dimensions
Height X Width X Depth
1690 x 1240 x 765 mm
1690 x 1240 x 765 mm
1690 x 1240 x 765 mm
Net Weight 279 kg
279 kg
279 kg
Refrigerant Type R410A
Charge 11.8 kg
11.8 kg
11.8 kg
Connection Pipe Diameter Liquid φ19.05 mm
Gas φ41.27 mm
Max. Height Difference
(Outdoor Unit: Upper/Lower)
50 / 40 m
Operation Range Cooling -5 to 52 °CDB
Heating -20 to 21 °CDB
Scroll

Dimensions

Outdoor Unit : AJH144LNTCH / AJH144LNTCH / AJH126LNTCH

Outdoor unit