VRF Systems V-III TROPICAL Series AJH450LNTCH
Features
- High ambient operation design
- Energy-saving technologies for boosting operational efficiency
- Elaborate anti-corrosion treatment
- Outstanding cooling capacity
Specifications
| Rated Capacity Range | 50 HP |
|---|---|
| Max. Number of Connectable Indoor Units*1 | 2 - 55 |
| Connectable Capacity of Indoor Units | 70.0 - 182.0 kW |
Scroll
| Power Source | Phase | 3 phase |
|---|---|---|
| Voltage | 380-415(50Hz),400(60Hz) V | |
| Frequency | 50/60 Hz | |
| Capacity | Cooling | 140.0 kW |
| Heating | 150.0 kW | |
| Input Power | Cooling | 42.58 kW |
| Heating | 40.89 kW | |
| EER | Cooling | 3.29 W/W |
| COP | Heating | 3.67 W/W |
| Airflow Rate | 13700 + 13700 + 13700 m³/h | |
| Sound Pressure Level*2 | Cooling | 67 dB(A) |
| Heating | 69 dB(A) | |
| Max. External Static Pressure | 82 Pa | |
| Compressor Motor Output | 11 x 1 + 11 x 1 + 11 x 1 kW | |
| Heat Exchanger Fin | Blue fin | |
| Net Dimensions Height X Width X Depth |
1690 x 1240 x 765 mm
1690 x 1240 x 765 mm 1690 x 1240 x 765 mm |
|
| Net Weight |
279 kg
279 kg 279 kg |
|
| Refrigerant | Type | R410A |
| Charge |
11.8 kg
11.8 kg 11.8 kg |
|
| Connection Pipe Diameter | Liquid | φ19.05 mm |
| Gas | φ41.27 mm | |
| Max. Height Difference (Outdoor Unit: Upper/Lower) |
50 / 40 m | |
| Operation Range | Cooling | -5 to 52 °CDB |
| Heating | -20 to 21 °CDB | |
Scroll
Dimensions
Outdoor Unit : AJH450LNTCH

India | English